30' - 0" x 11' - 0" x 9' - 0" "Straight" Type Manhole

Concrete:
  • 6,000 psi @ 28 days
  • 5% - 8% entrained air
Rebar:
ASTM A-615 grade 60 epoxy coated
Available duct entrances:
  • Single duct terminators to accept 6" Ø Sch 40 PVC Conduit or Custom Configurations And/Or Locations
Design criteria:
  • a) ASTM C858
  • b) Loading per ASTM C857, including:
  • -Earth cover: Min 1' - 0" Max 9' - 0"
  • -AASHTO HS-20 wheel load & applicable impact
  • -Vertical & lateral soil pressures determined using 120 PCF soil density
  • -Ground water at 3' - 0" below grade
  • c) Structural design performed using AASHTO strength design
  • d) Reinforcing cover per ACI 318
Weight:
  • a) Top section: 58,915#
  • b) Base section: 63,400#
  • c) 4' - 0" riser: 7,466# Each
  • d) Riser lid: 1,598# Each
  • e) Total manhole: 158,571#
Item Description Qty
1 Cable rack inserts: 1/2" Ø 304 stainless steel threaded inserts each with 1/2" Ø x 2" 304 S hex head bolt, 1/2" SS washer and 1/2" PVC washer 56
2 SS pulling irons 4
3 10T lifting anchors 8
4 20" Ø sump opening 2
5 1" butyl rubber joint sealant 16 Rolls
6 Rebar, epoxy coated
7 6" Ø duct terminator 48
8 2" ID PVC ground rod hole 4
9 1/4" Ø plastic threaded insert
1/4" x 1" hex head SS bolt
1/4" x 14" nylon strap
38
10 3/8" Ø galvanized steel threaded inserts 20
11 3/4" Ø galvanized steel threaded inserts 3
12 4T lifting anchors 24
Catalog PDF
Catalog PDF
Screen Friendly PDF
337kb
Printer Friendly PDF
394kb

You'll need Adobe Reader to view PDF files. You can download it here.