15' - 0" x 9' - 0" x 9' - 0" "Straight" Type Manhole

Concrete:
  • 5,000 psi @ 28 days
  • 5% - 8% entrained air
Rebar:
ASTM A-615 grade 60 epoxy coated
Available duct entrances:
  • Single duct terminators to accept
  • 5" Ø Sch 40 PVC conduit
Design criteria:
  • a) Meets ComEd* spec #C4381.C dated 5-1-95 and EM-14927 dated 9-1-92
  • b) ASTM C858
  • c) Loading per ASTM C857, including:
  • -Earth cover: Min 1' - 0" Max 5' - 0"
  • -AASHTO HS-20 wheel load & applicable impact
  • -Vertical & lateral soil pressures determined using 120 PCF soil density
  • -Ground water at 3' - 0" below grade
  • c) Structural design performed using AASHTO strength design
  • d) Reinforcing cover per ACI 318
Weight:
  • a) Top section: 26,160#
  • b) Base section: 23,670#
  • c) Total manhole: 49,830#
Item Description Qty
1 Cable rack inserts: 1/2" Ø 304 stainless steel threaded inserts each with 1/2" Ø x 2" 304 S hex head bolt, 1/2" SS washer and 1/2" PVC washer 32
2 SS pulling irons 2
3 8T lifting anchors 8
4 20" Ø sump opening 1
5 1" butyl rubber joint sealant 5 Rolls
6 Rebar, epoxy coated
7 5" Ø duct terminator 36
8 1" Ø x 5-1/2" ground wire hole 1/2" KO 2
9 1/4" Ø plastic threaded insert
1/4" x 1" hex head SS bolt
1/4" x 14" nylon strap
22
10 Ladder insert 3/8" Ø threaded carbon steel 4
Typical Install PDF
Typical Installation
Download the PDF
1,076kb

You'll need Adobe Reader to view PDF files. You can download it here.

Accessories PDF
Cast Iron Frame and Vented Cover
Screen Friendly PDF
263kb
Print Friendly PDF
281kb
Electrical Distribution Hardware Chart
Screen Friendly PDF
286kb
Print Friendly PDF
295kb

You'll need Adobe Reader to view PDF files. You can download it here.

Catalog PDF
Catalog PDF
Screen Friendly PDF
304kb
Printer Friendly PDF
336kb

You'll need Adobe Reader to view PDF files. You can download it here.

3x6x6 Manhole